Metadata-Version: 2.4
Name: intesis-gw-modbus
Version: 0.3.0
Summary: Intesis INMBS Modbus gateways for air conditioners, on modbus-connection.
Author-email: Timothy <6560631+TimoPtr@users.noreply.github.com>
License-Expression: Apache-2.0
Project-URL: Homepage, https://github.com/TimoPtr/intesis-gw-modbus
Project-URL: Repository, https://github.com/TimoPtr/intesis-gw-modbus
Project-URL: Issues, https://github.com/TimoPtr/intesis-gw-modbus/issues
Keywords: modbus,intesis,air-conditioner,mitsubishi-heavy-industries,home-assistant
Classifier: Development Status :: 3 - Alpha
Classifier: Intended Audience :: Developers
Classifier: Programming Language :: Python :: 3
Classifier: Programming Language :: Python :: 3.12
Classifier: Programming Language :: Python :: 3.13
Classifier: Programming Language :: Python :: 3.14
Classifier: Programming Language :: Python :: 3.15
Classifier: Topic :: Home Automation
Classifier: Typing :: Typed
Requires-Python: >=3.12
Description-Content-Type: text/markdown
License-File: LICENSE
Requires-Dist: modbus-connection[tmodbus]>=4.12.7
Provides-Extra: dev
Requires-Dist: pytest==9.2.0; extra == "dev"
Requires-Dist: pytest-asyncio==1.5.0; extra == "dev"
Requires-Dist: pytest-cov==7.1.0; extra == "dev"
Requires-Dist: ruff==0.17.5; extra == "dev"
Requires-Dist: mypy==2.4.1; extra == "dev"
Requires-Dist: yamllint==1.38.0; extra == "dev"
Provides-Extra: build
Requires-Dist: build==1.6.1; extra == "build"
Requires-Dist: twine==7.0.0; extra == "build"
Dynamic: license-file

# intesis-gw-modbus

Python library for [Intesis](https://www.intesis.com) INMBS Modbus gateways, the
boxes that put an air conditioner's indoor unit on a Modbus RTU or TCP bus.
Built on [modbus-connection](https://pypi.org/project/modbus-connection/): the
library models the registers and takes a `ModbusUnit`; it never opens a link.

This is an independent, community project. It is not affiliated with,
endorsed by or supported by HMS Networks, Intesis or any air-conditioner
manufacturer; Intesis and the gateway part numbers are their trademarks and are
used only to identify the hardware. The register maps come from the public user
manuals.

This library was built with the help of [Claude](https://claude.ai) (Anthropic).

## Supported gateways

| Gateway | Family | Status |
|---|---|---|
| INMBSMHI001R000 (Mitsubishi Heavy Industries, RTU) | single-unit | modelled from the manual (r6.4), verified against the mock backend |
| INMBSMHI048O000 / INMBSMHI128O000 (MHI, RTU or TCP) | multi-unit | modelled from the manual (r1.0), verified against the mock backend only |

The single-unit register map is shared by the other brands' `INMBSxxx001R000`
gateways. Their device ids are known (Daikin `0x0801`, Panasonic `0x1500`,
Toshiba `0x1F00`, LG `0x1000`, Hitachi `0x1400`, Samsung `0x1200`) but their
code and error tables are not written yet: see
[docs/adding-a-brand.md](docs/adding-a-brand.md).

### Single-unit gateways (INMBSxxx001R000)

One gateway per indoor unit, Modbus RTU only, configured with DIP switches.
The facts below come from the INMBSMHI001R000 manual; the other brands'
single-unit gateways are documented the same way but have not been checked.

- EIA-485, 8N2 by default (8N1 is auto-detected), 9600 baud and slave
  address 1 out of the box. SW3 sets the address and, with SW4, the baud rate
  (2400 to 115200); SW4 also sets the temperature format (x1 °C, x10 °C or °F)
  and switches in the on-board 120 Ω termination. Every DIP change needs a
  power cycle.
- SW1 sets the gateway's role on the air conditioner's XY bus: slave by
  default, which needs an MHI wired remote controller acting as master, or
  master, with any remote controller set as slave. Register 98 exposes the
  same role (`is_master`, `async_set_master`); the manual does not say which
  wins after a power cycle. As master the external temperature reference is
  applied directly; as slave the gateway shifts the setpoint to compensate.
- Function codes 3, 4, 6 and 16, with 16 limited to one register per request.
  A block read must not touch an undefined address, so the library reads the
  documented blocks only, one request each.

### Multi-unit gateways (INMBSxxx048O000 / INMBSxxx128O000)

One gateway for a whole MHI Superlink bus, configured with Intesis' LinkBoxMB
Windows tool rather than switches.

- Modbus TCP (port 502 by default) and/or Modbus RTU over EIA-485 or EIA-232
  (1200 to 38400 baud, parity selectable; the slave address is set in the tool).
- Function codes 3, 4 and 6 only. Each indoor unit owns a 20-register block
  and a poll of a range must stay inside valid addresses.

### Timing

The library asks for a 3 s request timeout on both families and a 20 ms gap
between requests on the single-unit gateway. These are conservative values
derived from the bus parameters, not measured; both live in the device
classes.

## Home Assistant

A core Home Assistant integration (`intesis_modbus`) built on this library is
in progress.

## Installation

```bash
pip install intesis-gw-modbus
```

Requires Python 3.12+ and `modbus-connection`.

## Usage

```python
import asyncio

from modbus_connection import ModbusSerialParams
from modbus_connection.tmodbus import ModbusConnection

from intesis_gw_modbus import (
    MODELS,
    FanSpeed,
    IntesisSingleUnitGateway,
    TemperatureFormat,
)


async def main() -> None:
    connection = ModbusConnection(
        ModbusSerialParams(device="/dev/ttyUSB0", baudrate=9600, stopbits=2)
    )
    try:
        unit = connection.for_unit(1)
        gateway = IntesisSingleUnitGateway(
            unit,
            brand=MODELS["INMBSMHI001R000"].brand,
            temperature_format=TemperatureFormat.DECICELSIUS,
        )
        report = await gateway.async_update()
        print(
            report.updated, gateway.mode, gateway.setpoint, gateway.current_temperature
        )
        await gateway.async_set_fan_speed(FanSpeed.HIGH)
        await gateway.async_set_setpoint(22.5)
    finally:
        await connection.close()


asyncio.run(main())
```

Every temperature the library returns or accepts is in degrees Celsius,
whatever the gateway's DIP-switch format. `detect_temperature_format(raw)`
infers the format from a raw setpoint register when it is not known. A
single-unit device applies the detected format after every poll, so the
`temperature_format` you construct it with only serves until the gateway
reports a setpoint, and a DIP-switch change is picked up by itself.

`async_probe_gateway(unit)` identifies a gateway before you build a device for
it. The returned `GatewayProbe` holds the single-unit `model` its device id
belongs to, the `unsupported_brand` of a documented gateway that has no table
yet, the detected `temperature_format`, and `vane_reported`, a hint that the
unit has a vane. Only single-unit gateways can be identified this way: a
multi-unit gateway keeps indoor unit readings at the same addresses, so it
comes back with no `model` and nothing else is read from it.

A multi-unit gateway is `IntesisMultiUnitGateway(unit, brand=..., unit_count=48)`;
after the first `async_update()` its `indoor_units` dict holds one
`IndoorUnitView` per unit the gateway talks to. Each unit's block is read on
its own, so one block failing only marks that unit not `present`. Each later
update re-probes the next 8 empty blocks, so a unit that comes online afterwards
joins the dict within a few polls; a unit that drops out stays listed with
`present` false.

## Development

```bash
pip install -e ".[dev]"
pytest            # 100 % coverage is enforced
mypy intesis_gw_modbus tests/
ruff check . && ruff format --check .
```

Everything runs against the `modbus-connection` mock backend; no hardware is
needed.

## Releasing

Publishing a GitHub release tagged `vX.Y.Z` builds the package from that tag
(the version comes from `setuptools-scm`) and publishes it to PyPI through
trusted publishing.

## License

Apache-2.0.